Skip to main content
Til toppen

DEHNrecord SD klasse A nettanalysator med webserver

Produktnummer: D910920
Lagerbeholdning:
ekskl. mva.

Un: 230/400V, DRC SD 1 1, Us 230V, måling i henhodl til EN 61000-4-30:2015, class A, uten display

Un: 230/400V, DRC SD 1 1, Us 230V, måling i henhodl til EN 61000-4-30:2015, class A, uten display

Integral, multifunctional measuring equipment based on edge computing with the following functions:

  • Supply voltage 230 V, 1-phase via L1, e.g. via busbar directly from surge arrester /no additional wiring or backup fuse required
  • Compact housing for simple integration and retrofitting, 5 modules in width / DIN rail mounting
  • Voltage quality measurement according to EN 61000-4-30, Class-A-certified
  • Permanent transmission of the standardised mean values
  • Fault record transmitted in the event of limit value violation / Resulting in significantly reduced data volume for easier handling
  • Limit values as per EN 50160 / option of additional definition of individual PQ limit values
  • Triggerable transmission of the fault record also without limit value violation / customised triggering via device button or Web-based
  • PQ characteristics as per marking concept according to EN 61000-4-30 
  • Four-pole load current and power measurement by means of external current coils for measurements of up to either 100 A (split-core current transformer) or up to 1,000 A (Rogowski coils) (cable lengths 3 m)
  • Measured value transmission of 5-minute mean values
  • Measurement with the correct polarity for detection of reference and regenerative power
  • Measurement of temporary / power-frequency overvoltages according to EN50550, including customised parameterisation options; e.g. for reporting low voltage
  • Event messages possible via cloud monitor, digital outputs and via email notifications
  • Integrated parameterizable I/O interfaces
  • 3x inputs, 2x outputs, for event-focussed control commands
  • Integrated measurement point concept
  • Adaptable by means of busbars directly to surge protective devices
  • Communication link via Modbus TCP/IP interface and MQTT protocol (3.1, Azure-based)
  • Measured value display either via DEHN Cloudmonitor or via external company-specific cloud platforms / Alternatively by reading from the Modbus register
  • GPS location positioning for possible creation of PQ maps
  • Web-based device configuration and firmware updates


 

Oprinnelses land Tyskland